High-voltage energy storage cabinet
JN-LFP48100-A
614.4 V / 61.44 kWh / 30 kW
A high-voltage LiFePO4 storage cabinet with 61.44 kWh nominal battery energy, 614.4 V nominal voltage and 30 kW cabinet power.
Specifications are taken from the supplied product materials. Confirm the current production revision and project compatibility before commissioning.

Air cooling and cabinet-level monitoring
Battery energy and AC power are specified separately
Air-cooled commercial energy storage
Separate battery energy from AC output when planning this cabinet. The battery is rated at 614.4 V, 100 Ah and 61.44 kWh, while the cabinet power is 30 kW with a three-phase connection. IP54 protection and intelligent air cooling are specified; battery and cabinet temperature limits are listed separately below.
Match the format to the site.
Technical data
Electrical ratings, dimensions and operating limits for this model. Battery energy and inverter power are listed separately where applicable.
| Nominal energy | 61.44 kWh |
|---|---|
| Nominal voltage | 614.4 V |
| Nominal capacity | 100 Ah |
| Cabinet rated power | 30 kW |
| Battery voltage range | 480.0–700.8 V |
| AC connection | Three-phase · 3W + N + PE |
| Frequency | 50 / 60 Hz |
| Standard charge current | 50 A |
| Standard discharge current | 50 A |
| Maximum charge current | 100 A |
| Maximum discharge current | 100 A (initial temperature ≤35°C) |
| Communications | RS485 / CAN / RS232 |
| Dimensions (L × W × H) | 1,100 × 700 × 1,350 mm |
| Net weight | 720 kg |
| Battery charge temperature | 0–55°C |
| Battery discharge temperature | −20–55°C |
| Cabinet operating temperature | −20–50°C |
| Cabinet storage temperature | −30–60°C |
| Cooling method | Intelligent air cooling |
| IP rating | IP54 |
| Battery chemistry | LiFePO4 |
| Charge mode | CC-CV |
Questions about this model
What are the nominal battery ratings?
A high-voltage LiFePO4 storage cabinet with 61.44 kWh nominal battery energy, 614.4 V nominal voltage and 30 kW cabinet power.
How should inverter compatibility be checked?
Match the exact voltage range, BMS protocol, charging limits and installation conditions. A brand name alone does not establish compatibility.
What should be confirmed before installation?
Use the operating limits below and confirm the current wiring and installation manual with JUNEXT before commissioning.
Do 61.44 kWh and 30 kW describe the same rating?
No. 61.44 kWh is nominal battery energy; 30 kW is cabinet power. The battery voltage is 614.4 V and the AC connection is three-phase. These values must not be used interchangeably.
One model. One verified document set.
Technical documents are available from JUNEXT on request. Confirm the product revision before installation.
Request current datasheetREQUESTCheck inverter compatibilityREQUESTAsk for installation guidanceREQUESTIs JN-LFP48100-A right for this project?
Share the destination market, essential loads, target backup time and inverter information. Juneng will help your installer validate the product direction.
Build a project brief